Mounting steps, Electrical installation – Lenze ERBM100R035W User Manual

Page 39

Advertising
background image

Electrical installation

Mounting steps

6

EDKRBM002 DE/EN/FR 4.0

39

l

H1_E_INST−ERBx_E_Inst_TXT_EN

Mounting steps

ERBMF006

How to connect the brake resistor:
1. Disconnect the basic device from the mains and check all

power terminals for safe isolation from supply.

2. Installing the brake resistor cable:

– Use twisted cables for a cable length up to 0.5 m

(connection plan version 1).

– Use shielded cables for a cable length up to 5 m

(connection plan version 2).

– Connect cores to the terminals RB1, RB2 and PE,

tightening torque must be observed. Connect PE
according to EN 61800−5−1.

– Apply cores and shield to the basic device; the

documentation of the basic device must be observed.

3. Installing the thermal contact cable:

– Use the twisted cable.
– Connect cores to the terminal T1 and T2; tightening

torque must be observed.

– When integrating the thermal contact into the system

monitoring ensure that the mains supply will be
switched off when the brake resistor is overheated.

Advertising