Lenze 9300 0.37kW-11kW User Manual

Page 18

Advertising
background image

Safety instructions

Safety instructions for the installation according to UL

2

l

18

EDKVS93−01 EN 3.0

2.4

Safety instructions for the installation according to UL

J

Warnings!

ƒ

Motor Overload Protection
– For information on the protection level of the internal overload protection

for a motor load, see the corresponding manuals or software helps.

– If the integral solid state motor overload protection is not used, external or

remote overload protection must be provided.

ƒ

Branch Circuit Protection
– The integral solid state protection does not provide branch circuit

protection.

– Branch circuit protection has to be provided externally in accordance with

corresponding instructions, the National Electrical Code and any
additional codes.

ƒ

Please observe the specifications for fuses and screw−tightening torques in
these instructions.

ƒ

EVS9321 … EVS9326:
– Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 480 V maximum, when protected by fuses.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 480 V maximum, when protected by CC, J, T or R
class fuses.

– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 75 °C copper wire only.

Advertising