Resetting system error messages, Troubleshooting and fault elimination – Lenze 9300 0.37kW-11kW User Manual

Page 45

Advertising
background image

Troubleshooting and fault elimination

System error messages

Resetting system error messages

4

l

45

EDKVS93−01 EN 3.0

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x252

AddData
DlErr

Error during FLASH memory
access

An error occurred when
downloading the data into the
FLASH memory (e.g. time−out,
transmission error, mains failure
during transmission)

Check/repeat data transfer.

x260

Err Node
Guard

"Life guarding event"

The controller configured as a
CAN slave does not receive a
"Node Guarding" telegram from
the CAN master within the "Node
Life Time".

l

Check wiring at X4.

l

Check CAN configuration.

l

Ensure that "node guarding"
has been activated in the CAN
master

l

Adapt the "node life time"
(C0383) to CAN master setting.

Explanation of the error numbers:
x

0 = TRIP, 1 = message, 2 = warning, 3 = FAIL−QSP
e.g. "2091": An external monitoring has triggered the warning EEr

4.3.2

Resetting system error messages

Reaction

Measures to reset the fault message

TRIP/ FAIL−QSP

Note!
If a TRIP/FAIL QSP source is still active, the pending TRIP/FAIL QSP cannot be reset.

The TRIP/FAIL QSP can be reset by:

l

pressing

ð S on keypad XT EMZ9371 BC. Then, press U to re−enable the controller.

l

Set code C0043 = 0.

l

Control word C0135, bit 11

l

Control word AIF

l

Control word system bus (CAN) / MotionBus (CAN) at ECSxS/P/M

After the reset of the TRIP/FAIL QSP, the drive remains at standstill.

Message

Danger!
The fault message is reset automatically after the fault has been eliminated, and the drive
restarts automatically.

Warning

After the fault has been eliminated, the fault message is reset automatically.