Troubleshooting and fault elimination

Troubleshooting

Fault analysis via LECOM status words (C0150/C0155)

4

l

35

EDKVS93−01 EN 3.0

4.2.3

Fault analysis via LECOM status words (C0150/C0155)

The LECOM status words (C0150/C0155) are coded as follows:

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0150 Status word

0

Device status word for networking
via automation interface (AIF)
Read only

0

{1}

65535 Controller evaluates information as

16 bits (binary−coded)

Bit 0

Not assigned

Bit 1

Pulse inhibit (IMP)

Bit2

Not assigned

Bit3

Not assigned

Bit4

Not assigned

Bit5

Not assigned

Bit 6

n = 0

Bit 7

Controller inhibit (CINH)

Bit 8

Device status bit 1

Bit 9

Device status bit 2

Bit10

Device status bit 3

Bit11

Device status bit 4

Bit12

Warning

Bit13

Message

Bit14

Not assigned

Bit15

Not assigned

C0155 Status word 2

0

Status word 2 (advanced status
word)
Display only

0

{1}

65535 Controller interprets information as

16 bit (binary coded)

Bit 0

Active fault

Bit 1

M

max

reached

Bit 2

I

max

reached

Bit 3

Pulse inhibit(IMP)

Bit 4

Ready for operation (RDY)

Bit 5

Controller inhibit (CINH)

Bit 6

TRIP active

Bit 7

Initialisation

Bit 8

Motor direction of rotation (Cw/CCw)

Bit 9

Not assigned

Bit 10

Not assigned

Bit 11

Not assigned

Bit 12

Not assigned

Bit 13

Not assigned

Bit 14

Not assigned

Bit 15

Not assigned