Troubleshooting and fault elimination

System error messages

General error messages

4

l

41

EDKVS93−02 EN 3.0

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x091

EEr

External monitoring has been
triggered via DCTRL.

A digital signal assigned to the
TRIP−SET function has been
activated.

l

Check external encoder.

l

Switch off the monitoring
(C0581 = 3).

0105

H05

Internal fault (memory)

Contact Lenze.

0107

H07

Internal fault (power stage)

During initialisation of the
controller, an incorrect power
stage was detected.

Contact Lenze.

x110

H10

Heatsink temperature sensor
error

Sensor for detecting the heatsink
temperature indicates undefined
values.

l

Contact Lenze.

l

Switch off the monitoring
(C0588 = 3).

x111

H11

Temperature sensor error:
Temperature inside the controller

Sensor for detecting the internal
temperature indicates undefined
values.

l

Contact Lenze.

l

Switch off the monitoring
(C0588 = 3).

x151

P01

Error "negative limit switch".

Negative limit switch was
reached.

l

Control drive in positive
direction

l

Check wiring at X5/E2.

x152

P02

Error "positive limit switch".

Positive limit switch was reached.

l

Control drive in negative
direction

l

Check wiring at X5/E1.

x153

P03

Following error

The angle difference between set
and actual position is larger than
the following error limit set under
C0255.

l

Increase following error limit
under C0255.

l

Switch off the monitoring
(C0589 = 3).

Drive cannot follow the digital
frequency (I

max

limit).

Check drive dimensioning.

x154

P04

Error "negative position limit".

Negative position limit (C1224)
was not reached.

Find out why the value was not
reached (e.g. "incorrect" position
targets, set function position
value) and adjust the position
limit in C1224 if necessary.

x155

P05

Error "positive position limit".

Positive position limit (C1223)
was exceeded.

Find out why the value was
exceeded (e.g. "incorrect" position
targets, set function position
value) and adjust the position
limit in C1223 if necessary.

x156

P06

No reference.

The reference point is not known.
In the case of absolute
positioning, no homing was
performed before the first
positioning.

Perform one of the following
functions and restart:

l

Manual homing.

l

Start homing in the program.

l

Set reference.

x157

P07

Parameter set mode is absolute
instead of relative.

An absolute parameter set
(C1311) was performed during
relative positioning (position
mode C1210).

Perform one of the following
functions and restart:

l

Change the parameter set
from absolute to relative.

l

Change position mode.

x158

P08

Error "actual reference dimension
offset".

Actual reference dimension offset
(C1226) outside the position
limits. Error of the program
function "set position value".

If necessary, adapt the position
limit values or check whether the
program function "set position
value" is to be applied.

x159

P09

Error in positioning program.

Impermissible programming

Check position program:

l

A parameter set with final
speed must be followed by a
parameter set with
positioning; it is not
permissible to wait for input.