System error messages, General error messages, Troubleshooting and fault elimination – Lenze VS9332−xx User Manual

Page 36: System error messages general error messages

Advertising
background image

Troubleshooting and fault elimination

System error messages
General error messages

4

l

36

EDKVS93−03 EN 3.0

4.3

System error messages

4.3.1

General error messages

)

Note!

In the case of a query via system bus (CAN), the fault messages are
represented as numbers (see first column of the table).

Fault message

Description

Cause

Remedy

No.

Display

−−−

−−−

No fault

0011

OC1

Short circuit of motor cable

Short circuit

l

Search for cause of short
circuit.

l

Check motor cable.

Excessive capacitive charging
current in the motor cable.

Use motor cable which is shorter
or of lower capacitance.

0012

OC2

Motor cable earth fault

One of the motor phases has
earth contact.

l

Search for cause of short
circuit.

l

Check motor cable.

0015

OC5

I x t overload

l

Frequent and too long
acceleration with overcurrent

l

Continuous overload with
I

motor

> 1.05 x I

rx.

Check drive dimensioning.

0016

OC6

I

2

xt overload

l

Frequent and too long
acceleration processes with
motor overcurrent.

l

Permanent motor overload
with I

motor

>I

rmotor

Check drive dimensioning.

x018

OC8

I

2

xt overload advance warning

l

Frequent and too long
acceleration processes with
motor overcurrent.

l

Permanent motor overload
with I

motor

>I

rmotor

Check drive dimensioning.

1020

OU

Overvoltage in DC bus

Braking energy is too high.
(DC−bus voltage is higher than set
in C0173.)

l

Use braking unit or
regenerative module.

l

Check dimensioning of the
brake resistance.

1030

LU

Undervoltage in the DC bus

DC bus voltage is lower than
specified in C0173.

l

Check mains voltage

l

Check supply cable

x032

LP1

Motor phase failure

A current−carrying motor phase
has failed.

l

Check motor.

l

Check motor cable.

l

Switch off monitoring
(C0597 = 3).

The current limit value is set too
low.

l

Set higher current limit value
via C0599.

0050

OH

Heatsink temperature > +90

C

Ambient temperature
T

u

> +40

C or > +50 C

l

Allow module to cool and
ensure better ventilation.

l

Check ambient temperature in
the control cabinet.

Heatsink is very dirty.

Clean heatsink.

Wrong mounting position

Change mounting position.