Troubleshooting and fault elimination

System error messages

General error messages

4

l

43

EDKVS93−03 EN 3.0

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x168

P18

Internal limitation.

Arithmetic operation generated
data cannot be varied arbitrarily.
Wrongly specified values were
automatically limited internally.
C1298 = 1:
The negative position limit in
C1223 is outside the possible
display range of
1

£ (C1223 × C1205) £ 1.07E9 inc

Check the values in C1202/4,
C1207/1, C1207/2. Read out the
limited value in C1220/10 and
enter it in C1223 if necessary.

C1298 = 2:
The positive position limit in
C1224 is outside the possible
display range of
1

£ (C1224 × C1205) £ 1.07E9 inc

Check the values in C1202/4,
C1207/1, C1207/2. Read out the
limited value in C1220/11 and
enter it in C1224 if necessary.

C1298 = 3:
The maximum speed v

max

in

C1240 is outside the possible
display range of
1

£ (C1240 × C1205 ×

16.384)

£ 2.14E9 inc or v

max

not

C1240 / C1204 Ч 60

£ 1.5 Ч n

max

Check the values in C0011,
C1202/4, C1207/1, C1207/2. Read
out the limited value in C1220/12
and enter it in C1240 or adjust the
value in C1240 to C0011 if
necessary.

C1298 = 4:
The maximum acceleration a

max

in C1250 is outside the possible
display range of
1

£ (C1250 × C1205 × 16.384 / 10

00)

£ 2.8634E7 inc

Check the values in C1202/4,
C1207/1, C1207/2. Read out the
limited value in C1220/13 and
enter it in C1250 if necessary.

C1298 = 5:
An internal value range has been
exceeded for a speed
standardisation. Valid range:
1

£ (C0011 × C1207/1 / C1207/2

65536 / 60000)

£ 32767

Check the values in C0011,
C1207/1, C1207/2 and correct
them.

x169

P19

The input values at X9 are limited. The function block DFIN limits the

input values. This causes the loss
of increments.

l

Reduce the frequency on the
digital frequency connection.

l

Check the settings for the slave
(C0425) and for the master
(C0030). These settings must
be identical.

x171

P21

Following error.

The phase difference between set
and actual position is larger than
the following error limit set under
C1328.

l

Extend the following error
limit under C1328.

l

Switch off monitoring
(C1329=3).

Drive cannot follow the digital
frequency (I

max

limit).

Check drive dimensioning.

x190

nErr

Speed control error
(Speed out of tolerance margin
(C0576))

l

Active load (e.g. for hoists) is
too high.

l

Mechanical blockades on the
load side

Check drive dimensioning.

x200

NMAX

Maximum system speed (C0596)
has been exceeded.

l

Active load (e.g. for hoists) is
too high.

l

Drive is not speed−controlled,
torque is excessively limited.

l

Check drive dimensioning.

l

Increase torque limit, if
necessary.

l

Switch off monitoring
(C0607 = 3).

0201

overrun
Task1

Time−out in task 1 (ID 2)

Task processing takes longer than
the monitoring time set.

l

Adjust the length of the task
runtime.

l

Adjust monitoring time.

l

Determine the cause of
time−out by checking the task
runtime at the task monitor.

l

Swap out time−critical program
parts in a slower task.

...

...

...

0208

overrun
Task8

Time−out in task 8 (ID 9)