Troubleshooting and fault elimination, System error messages general error messages – Lenze VS9332−xx User Manual

Page 38

Advertising
background image

Troubleshooting and fault elimination

System error messages
General error messages

4

l

38

EDKVS93−03 EN 3.0

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x065

CE4

BUS−OFF state of system bus
(CAN)

The controller has received too
many faulty telegrams via the
system bus (CAN) and has
disconnected from the bus.

l

Check wiring at X4: Is the bus
correctly terminated?

l

Check shield connection of the
cables.

l

Check PE connection.

l

Check bus load, reduce the
baud rate if necessary.
(Observe the cable length!)

l

Switch off the monitoring
(C0595 = 3).

x066

CE5

Time−out of system bus (CAN)
(communication error of gateway
function)

For remote parameterisation
(C0370, C0371) via system bus
(CAN):

l

Slave does not respond.

l

Communication monitoring
time has been exceeded.

l

Check wiring of system bus
(CAN).

l

Check CAN bus configuration.

0070

U15

Undervoltage of internal 15 V
voltage supply

Check voltage supply.

0071

CCr

System failure

Strong interference injection on
the control cables

Screen control cables

Ground or earth loops in the
wiring

l

Check wiring

l

Check PE connection

After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!

0072

PR1

Checksum error in parameter
set 1
CAUTION: The Lenze setting is
loaded automatically!

l

Fault when loading a
parameter set.

l

Interruption while
transmitting the parameter set
via keypad.

l

Set the required parameters
and store them under C0003 =
1.

l

As to PLC devices, check the
use of pointers.

The stored parameters are
incompatible with the loaded
software version.

Store the parameter set under
C0003 = 1 first to allow for a
faults reset.

0073

PR2

Checksum error in parameter
set 2
PLEASE NOTE: The Lenze setting is
loaded automatically!

l

Fault while loading a
parameter set.

l

Interruption during the
transfer of the parameter set
via keypad.

l

Set the required parameters
and save them with C0003 = 2.

The parameters saved do not
comply with the software version
loaded.

In order to be able to
acknowledge the error, first save
the parameter set with C0003 = 2.

0074

PEr

Program error

Error in the program flow

Send the parameter set (on floppy
disk/CD−ROM) with a detailed
description of the problem to
Lenze.
After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!

0075

PR0

Error in parameter set.

The operating system software
has been updated.

Storage of the Lenze setting
C0003 = 1.

After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!

0077

PR3

Checksum error in parameter
set 3
PLEASE NOTE: The Lenze setting is
loaded automatically!

l

Fault while loading a
parameter set.

l

Interruption during the
transfer of the parameter set
via keypad.

l

Set the required parameters
and save them with C0003 = 3.

The parameters saved do not
comply with the software version
loaded.

In order to be able to
acknowledge the error, first save
the parameter set with C0003 = 3.