6 electrical installation, Important notes, Connection data – Lenze ERBMxxxRxxxx User Manual

Page 35: Connection plan, Electrical installation, Stop

Advertising
background image

Electrical installation

Important notes

6

EDKRBM470R DE/EN/FR 5.0

35

l

H1_E_INST−eInstall_EN

6

Electrical installation

Important notes

(

Stop!

Possible overheating of the brake resistor during
operation

Inadequate heat dissipation during operation can
cause the brake resistor to overheat.

Possible consequences:

ƒ

The brake resistor is destroyed.

ƒ

The drive is not braked but coasts to a standstill.

Protective measures:

ƒ

Always connect the thermal contact of the brake
resistor.

ƒ

Integrate the thermal contact into the overall
equipment monitoring apparatus in such a way
that the supply of power to the standard device is
switched off if the brake resistor overheats (e.g.
switch−off by means of mains contactor control).

Connection data

Cable cross−section

Brake resistor

Thermal contact

[mm

2

]

AWG

[mm

2

]

AWG

ERBMxxxRxxxW

2.1

14

0.75

18

Connection plan

Variant 1: without cable extension

R

B

f

PE

ERBMXXX012

Twisted cables

s

Length of prepared cables

^ 33

Advertising