Electrical installation, Stop – Lenze EPM−H310 User Manual

Page 53

Advertising
background image

Electrical installation

Wiring of the system bus (CAN)

4

l

53

EDBPM−H310 DE/EN/FR 7.1

Terminal assignment

(

Stop!

Connect a 120

W terminating resistor to the first and last bus device.

Terminal

Identification

Explanation

1

V−

GND

Reference potential

2

CAN−

LO

System bus LOW (data line)

3

Shield

Connect the shield of the system bus cable

4

CAN+

HI

System bus HIGH (data line)

5

n.c.

Not connected

For trouble−free operation, use cables with the listed specifications:

Cable specifications

Overall length

£ 300 m

£ 1000 m

Cable type

LIYCY 2 x 2 x 0.5 mm

2

(twisted in pairs and shielded cores)

CYPIMF 2 x 2 x 0.5 mm

2

(twisted in pairs and shielded cores)

Cable resistance

£ 80 W/km

£ 80 W/km

Capacitance per unit
length

£ 130 nF/km

£ 60 nF/km

Advertising