Commissioning

Manual control
Checking the configuration

6

6.10
6.10.2

l

6.10−2

EDSVS9332P EN 5.0−07/2013

6.10.2

Checking the configuration

Check a new or changed configuration in manual operation with regard to
a faultless function.

}

Danger!

Uncontrolled motor movement possible.
Incorrect settings in the configuration may cause uncontrolled
movements.
Possible consequences:

ƒ

Severe injuries to persons in or near the machine.

ƒ

The machine is damaged or destroyed.

Protective measures:

ƒ

Provide suitable emergency off equipment so that you are
able to shut down the drive immediately.

1
2
3

4

5

6

Fig. 6.10−2

"Control" dialog box

Procedure

1.

Activate "Manual operation" (3).

2.

Click "Start" (4) to enable the controller.

l

If "Ok" is displayed in the "Drive diagnostics" field (5), controller enable can be
executed.

l

Controller inhibit must be deactivated (X5/28 = HIGH).

3.

Move the drive against the travel range limit switches, in order to check its function.

l

"Pos. manual" (2) or "Neg. manual" (1) is activated: The drive traverses.

l

"Pos. manual" (2) or "Neg. manual" (1) is deactivated: The drive stops.

A

Activate "Pos. manual" (2).

l

The drive traverses in the direction of the positive travel range limit switch.

B

Activate "Neg. manual" (1).

l

The drive traverses in the direction of the negative travel range limit switch.