N2 points – Lenze MCH Series Drives Metasys N2 User Manual

Page 10

Advertising
background image

7

RG-MHMET

N2 Points

4.2 Analog Input (AI) Point Descriptions

Point

Description

1-01:

Actual Frequency

This point represents the actual speed of the drive in Hz.

1-02:

Command Frequency

This point represents the commanded drive speed in Hz.

1-03:

Load Percent

This point represents the drive’s load current as a % of rated current. This value can also
be seen on the local display.

1-04:

Total Runtime

This point represents the number of hours that the drive has been running since its first
power-up.

1-05:

DC Bus Voltage

This point represents the drive's DC Bus Voltage as a percentage of the nominal DC bus
voltage.

1-06:

Operational Status

This point is for monitoring the actual operating condition of the drive. The value returned
is a number between 0 and 10 which corresponds to one of the following operating states:

Value

Operational State

0

FAULT LOCKOUT

1

FAULT

2

START PENDING

3

STOP

4

DC BRAKE

5

RUN AT 0Hz

6

RUN

7

ACCEL

8

DECEL

9

CURRENT LIMIT

10

DECEL OVERRIDE

1-07:

H/O/A Mode

This point is for monitoring the drive H/O/A status. If the drive H/O/A is OFF, this point
will return 0 and serial speed/setpoint and serial start commands will not be accepted.
If the drive H/O/A is HAND, this point will return 1 and serial speed/setpoint and serial
start commands will not be accepted. If the drive H/O/A is AUTO, this point will return 2
and, depending on the setting of Drive Parameter #30 (Control), serial speed/setpoint and
serial start commands will be accepted. For more information, refer to Section 3.1 Serial
Communication Setup.