N2 points, 4mch n2 points, 1 metasys n2 point map – Lenze MCH Series Drives Metasys N2 User Manual

Page 9: Rg-mhmet 6

Advertising
background image

RG-MHMET

6

N2 Points

4

MCH N2 Points

The MCH N2 Points are divided into four types: analog input, binary input, analog output and binary output.
Sections 4.2 through 4.5 describe each of these point types and the individual point numbers within each.

4.1 Metasys N2 Point Map

Table 2: Metasys N2 Point Map for MCH Series Drives

Point

Type

1

Point

#

COS

2

Status
Point

3

Description (Point Name)

Point
Units

Decimal

Places

MIN

Value

MAX

Value

Default

Value

1

01

Yes

Yes

Actual Frequency (OUTPUT FREQ)

HZ

2

0

12000

0

1

02

Yes

Yes

Command Frequency (COMMAND FREQ)

HZ

2

0

12000

2000

1

03

Yes

Yes

Load Percent (LOAD PERCENT)

PCT

0

0

255

0

1

04

Yes

Yes

Total Runtime (RUNTIME HRS)

HRS

0

0

65535

0

1

05

Yes

Yes

DC Bus Voltage (DC BUS VOLTS)

PCT

0

0

255

0

1

06

Yes

Yes

Operational Status (RUN STATUS)

--

0

0

10

3

1

07

Yes

Yes

H/O/A Mode (HOA MODE)

--

0

0

2

0

1

08

Yes

Yes

PID Setpoint Command (PID SETPOINT)

Note 4

0

Note 4

Note 4

50

1

09

Yes

Yes

PID Feedback (PID FEEDBACK)

Note 4

0

Note 4

Note 4

0

1

10

Yes

Yes

Present Fault (FAULT)

--

0

0

24

0

2

01

Yes

Yes

PID Mode (PID MODE)

--

--

DIS

ENA

DIS

2

02

Yes

Yes

Current Direction (FWD.REV)

--

--

FWD

REV

FWD

2

03

Yes

Yes

Run/Stop Status (RUN.STOP)

--

--

STP

RUN

STP

2

04

Yes

Yes

TB-14 / Relay #2 (TB14.RELAY2)

--

--

OFF

ON

OFF

2

05

Yes

Yes

TB-15 / Relay #3 (TB15.RELAY3)

--

--

OFF

ON

OFF

2

06

Yes

Yes

Relay #1 (RELAY1)

--

--

OFF

ON

OFF

2

07

Yes

Yes

Fault Condition (OK.FAULT)

--

--

OK

FLT

OK

2

08

Yes

Yes

Serial Watchdog (SERIAL WATCHDOG)

--

--

ENA

DIS

ENA

3

01

Yes

No

Acceleration Rate (ACCEL RATE)

SEC

1

0

36000

300

3

02

Yes

No

Deceleration Rate (DECEL RATE)

SEC

1

0

36000

300

3

03

Yes

No

Speed Source Selection (SOURCE SEL)

--

0

0

2

0

3

04

Yes

No

Keypad Speed Command (KEY SPD CMD)

HZ

2

0

12000

2000

3

05

Yes

No

Keypad Setpoint Command (KEY STPT CMD)

Note 4

0

Note 4

Note 4

50

4

01

Yes

No

Start/Stop Drive (CMD RUN.STOP)

--

--

STP

RUN

STP

4

02

Yes

No

Disable Serial Watchdog (DIS SER WATCHDOG)

--

--

NRM

DIS

NRM

4

03

Yes

No

Clear Present Fault (CLEAR FAULT)

--

--

NRM

RST

NRM

NOTES:
1. Point Types: 1= AI (Analog Input); 2 = BI (Binary Input); 3 = AO (Analog Output); 4 = BO (Binary Output)

2. COS: Change of State

3. Status Points: for monitoring purposes only and cannot be overridden; Yes = Point can be used as a

status point; No = Point cannot be used as a status point.

4. Units, MIN/MAX Values: for this point are defined via Drive Parameters #31, 75 and 76 respectively.

Refer to notes in sections 4.2 and 4.4.

Advertising