N2 points – Lenze MCH Series Drives Metasys N2 User Manual

Page 11

Advertising
background image

RG-MHMET

8

N2 Points

Point

Description

1-08:

PID Setpoint Command

This point is for monitoring the commanded PID Setpoint and is displayed in the drive’s
internal PID units with a range of 0-32736. A value of 0 represents the lower of Drive
Parameter #75 (Feedback @ Min) and Drive Parameter #76 (Feedback @ Max). A value
of 32736 represents the higher of Drive Parameter #75 (Feedback @ Min) and Drive
Parameter #76 (Feedback @ Max).

1-09:

PID Feedback

This point is for monitoring the current PID Feedback value at the input specified by Drive
Parameter #74 (PID Feedback). It is displayed in the drive’s internal PID units with a range
of 0-32736. A value of 0 represents the lower of Drive Parameter #75 (Feedback @ Min)
and Drive Parameter #76 (Feedback @ Max). A value of 32736 represents the higher of
Drive Parameter #75 (Feedback @ Min) and Drive Parameter #76 (Feedback @ Max).

1-10:

Present Fault

This point indicates the type of fault on which the drive is currently tripped. This point returns
a value between 0 and 24 which corresponds to one of the following fault conditions:

Value

Fault

0

NO FAULT

1

OUTPUT FAULT

2

E-STOP

3

HIGH DC BUS VOLTS

4

HIGH DRIVE TEMPERATURE

5

THERMAL OVERLOAD

6

OUTPUT FAULT

7

LOW DC BUS VOLTS

8

START ERROR

9

DC BRAKE ERROR

10

FOLLOWER LOSS

11

DB ERROR

12

POWER SAG

13

CONTROL FAULT

14

LANGUAGE

15

EXTERNAL FAULT

16

INTERNAL16

17

POWER TRANSIENT

18

S/W ERROR #1

19

S/W ERROR #2

20

S/W ERROR #3

21

S/W ERROR #4

22

S/W ERROR #5

23

GENERAL S/W ERROR

24

SERIAL COMMUNICATION LOSS