RG-MHSP1F

P1 Points

4

MCH P1 Points

Any sub-point that can be commanded is an OUTPUT (LDO or LAO). Any sub-point that cannot be commanded
is an INPUT (LDI or LAI).

When an LAO point is unbundled (or characterized), the initial value used to unbundle it must be within
the defined boundaries of the point. For example: the initial value for Point #36 (KEY SPD CMD) must be
defined as follows:

Drive Parameter #10 (Minimum Freq) <= Initial Value <= Drive Parameter #11 (Maximum Freq).

If an invalid initial value is used, the unbundled point will always report a FAIL status. This point must be
removed and re-characterized with a valid initial value.

4.1 MCH P1 Point Map

Table 2: Siemens P1® Point Map for MCH Series Drives

Point

#

Point

Type

Description (P1 Point Name)

ENG/SI

Units

ENG/SI

Slope

ENG/SI

Intercept

ENG/SI On

Text

ENG/SI Off

Text

Default

Value

01

LAO

Serial Address (CTRL ADDRESS)

--

1.00

0

--

--

99

02

LAI

Application Number (APPLICATION)

--

1.00

0

--

--

2726

[03]

LAI

Actual Frequency (OUTPUT FREQ)

HZ

0.01

0

--

--

0

[04]

LAI

Actual Percent Output (OUTPUT PCT)

PCT

1.00

0

--

--

0

[05]

LAI

Actual Speed (OUTPUT SPEED)

RPM

1.00

0

--

--

0

[07]

LAI

Load Percent (LOAD PERCENT)

PCT

1.00

0

--

--

0

[08]

LAI

Command Frequency (COMMAND FREQ)

HZ

0.01

0

--

--

2000

[09]

LAI

Command Percent Output (COMMAND PCT)

PCT

1.00

0

--

--

33

[10]

LAI

Command Speed (COMMAND SPD)

RPM

1.00

0

--

--

600

11

LAI

Software Version (SOFTWARE VER)

--

1.00

0

--

--

Varies

[12]

LAI

Total Runtime (RUNTIME HRS)

HRS

1.00

0

--

--

0

[13]

LAI

DC Bus Voltage (DC BUS VOLTS)

PCT

1.00

0

--

--

0

[14]

LAI

Operational Status (RUN STATUS)

--

1.00

0

--

--

3

[15]

LAI

H/O/A Mode (HOA MODE)

--

1.00

0

--

--

0

16

LDI

PID Mode (PID MODE)

--

1.00

--

ENABLE

DISABL

0

[17]

LAI

PID Setpoint Command (PID SETPOINT)

--

1.00

0

--

--

16368

[18]

LAI

PID Feedback (PID FEEDBACK)

--

1.00

0

--

--

0

20

LAO

Day/Night Override Time (OVRD TIME)

HRS

1.00

0

--

--

1

[21]

LDI

Current Direction (FWD.REV)

--

1.00

--

REV

FWD

0

[23]

LDI

Run/Stop Status (RUN.STOP)

--

1.00

--

RUN

STOP

0

[24]

LDO

Start/Stop Drive (CMD RUN.STOP)

--

1.00

--

RUN

STOP

0

[29]

LDO

Day/Night Operation (DAY.NIGHT)

--

1.00

--

NIGHT

DAY

0

31

LAO

Acceleration Rate (ACCEL RATE)

SEC

0.10

0

--

--

300

32

LAO

Deceleration Rate (DECEL RATE)

SEC

0.10

0

--

--

300

[34]

LAO

Speed Source Selection (SOURCE SEL)

--

1.00

0

--

--

0

[36]

LAO

Keypad Speed Command (KEY SPD CMD)

HZ

0.01

0

--

--

2000

[37]

LAO

Keypad Setpoint Command (KEY STPT CMD)

--

1.00

0

--

--

16368

[40]

LDI

TB-14 / Relay #2 (TB14.RELAY2)

--

1.00

--

ON

OFF

0

Advertising