2 mch p1 point descriptions, Mch p1 point descriptions, P1 points – Lenze MCH Series Drives Siemens P1 User Manual

Page 11: Rg-mhsp1f 8

Advertising
background image

RG-MHSP1F

8

P1 Points

Point

#

Point

Type

Description (P1 Point Name)

ENG/SI

Units

ENG/SI

Slope

ENG/SI

Intercept

ENG/SI On

Text

ENG/SI Off

Text

Default

Value

[41]

LDI

TB-15 / Relay #3 (TB15.RELAY3)

--

1.00

--

ON

OFF

0

[42]

LDI

Relay #1 (RELAY1)

--

1.00

--

ON

OFF

0

[92]

LAI

Present Fault (FAULT)

--

1.00

0

--

--

0

[93]

LDI

Fault Condition (OK.FAULT)

--

1.00

--

FAULT

OK

0

[94]

LDO

Clear Present Fault (CLEAR FAULT)

--

1.00

--

RESET

NORMAL

0

99

LAI

Error Status Flags (ERROR STATUS)

--

1.00

0

--

--

0

NOTES:
1. Point numbers that appear in brackets [ ] may be unbundled at the field panel.
2. Point Types: LDI = Logical Digital Input, LDO = Logical Digital Output,

LAI = Logical Analog Input, LAO = Logical Analog Output

4.2 MCH P1 Point Descriptions

Point 1:

This point reflects the serial address of the drive. As stated earlier, this point is selectable up
to 99 but should only be set in the range of 1-98 when on the LAN.

Point 2:

This point contains the number of the current application. Since this point currently only has
one value, that being 2726, this point is not capable of being commanded.

Point 3:

This point is for monitoring the actual speed of the drive in Hz.

Point 4:

This point is for monitoring the actual speed of the drive as a percentage of the value set in
Drive Parameter #11 (Maximum Freq). It is rounded to the nearest whole number.

Point 5:

This point is for monitoring the actual speed of the drive in RPMs. The value returned by this
point is the actual drive speed in Hz multiplied by the value set in Drive Parameter #32 (Hz
Multiplier) and rounded to the nearest whole number.

Point 7:

This point is for monitoring the drive’s load current as a % of rated current.

Point 8:

This point is for monitoring the commanded drive speed in Hz.

Point 9:

This point is for monitoring the commanded drive speed as a percentage of the value set in
Drive Parameter #11 (Maximum Freq). It is rounded to the nearest whole number.

Point 10: This point is for monitoring the commanded drive speed in RPMs. The value returned by this

point is the commanded drive speed in Hz multiplied by the value set in Drive Parameter #32
(Hz Multiplier) and rounded to the nearest whole number.

Point 11: This point returns the software version (including the current revision) of the drive firmware.

This information can also be obtained from Drive Parameter #63 (Software Version). For
example, drive software version MC09803 will be displayed as 9803.

Point 12: This point is for monitoring the number of hours that the drive has been running since its first

power-up.

Advertising