3 reference and links, Reference and links, P1 points – Lenze MCH Series Drives Siemens P1 User Manual

Page 15

Advertising
background image

RG-MHSP1F

12

P1 Points

Point 92: This point indicates the type of fault on which the drive is currently tripped. This point returns

a value between 0 and 24 which corresponds to one of the following fault conditions:

VALUE

FAULT

VALUE

FAULT

0

NO FAULT

13

CONTROL FAULT

1

OUTPUT FAULT

14

LANGUAGE

2

E-STOP

15

EXTERNAL FAULT

3

HIGH DC BUS VOLTS

16

INTERNAL16

4

HIGH DRIVE TEMPERATURE

17

POWER TRANSIENT

5

THERMAL OVERLOAD

18

S/W ERROR #1

6

OUTPUT FAULT

19

S/W ERROR #2

7

LOW DC BUS VOLTS

20

S/W ERROR #3

8

START ERROR

21

S/W ERROR #4

9

DC BRAKE ERROR

22

S/W ERROR #5

10

FOLLOWER LOSS

23

GENERAL S/W ERROR

11

DB ERROR

24

SERIAL COMMUNICATION LOSS

12

POWER SAG

Point 93: This point indicates whether or not the drive is currently tripped on a fault. This point returns

OK (0) if the drive is not in a fault condition or FAULT (1) if it is.

Point 94: This point is used to clear the current fault through the FLN. Set this point to RESET (1) to clear

the present fault. Once the fault has been cleared, the value of this point will automatically
return to NORMAL (0).

Point 99: This point is not used by the MCH Series P1 drive and is, therefore, not capable of being

commanded. When read, this point will always return a value of 0.

4.3 Reference and Links

MCH Series Variable Frequency Drives visit:

http://www.lenze-actech.com

Siemens Building Technologies visit:

http://www.buildingtechnologies.usa.siemens.com/

The APOGEE Building Automation System visit:

http://www.buildingtechnologies.usa.siemens.com/Products__and__Systems/Building_
automation_and_control/APOGEE_Building_Automation_System/Overview/standard_
protocols.htm

Advertising