Electrical installation

Important notes

(

Stop!

Possible overheating of the brake resistor during operation

Inadequate heat dissipation during operation can cause the brake resistor to
overheat.

Possible consequences:

ƒ

The brake resistor is destroyed.

ƒ

The drive is not braked but coasts to a standstill.

Protective measures:

ƒ

Always connect the thermal contact of the brake resistor.

ƒ

Integrate the thermal contact into the overall equipment monitoring
apparatus in such a way that the supply of power to the standard device is
switched off if the brake resistor overheats (e.g. switch−off by means of
mains contactor control).

Connection data

Cable gland

Type of

connection

Size of connection Tightening torque

RB1, RB2
(brake resistor)

M25

Screw terminal

0.5 ... 10 mm

2

20 ... 6 AWG

1.5 ... 1.8 Nm

13.3 ... 15.9 lb−in

PE
(PE conductor)

Screw

M4

2.2 ... 2.7 Nm

19.5 ... 23.9 lb−in

T1, T2
(thermal contact)

M12

Screw terminal

0.25 ... 4 mm

2

24 ... 12 AWG

0.6 ... 0.8 Nm

5.3 ... 7.1 lb−in