Mounting steps, 6electrical installation – Lenze ERBSxxxxxxxx User Manual

Page 52

Advertising
background image

6

Electrical installation

Mounting steps

EDKRBS047R DE/EN/FR/ES/IT 8.0

52

l

H1_E_INST−eInstall_EN

Mounting steps

1

0

RB1

T1
T2

RB2

PE

ERBS103

How to connect the brake resistor:
1. Disconnect the basic device from the mains and check that no voltage is applied to

the power terminals.

2. Remove the terminal cover.
3. Connect the brake resistor cable:

– Use a twisted cable for cables up to 0.5 m (connection plan variant 1).
– Use a shielded cable for cables up to 5 m (connection plan variant 2).
– Pass the cable through the cable gland

0.

– Connect the cores to connections RB1, RB2 and PE of the brake resistor observing

the tightening torque. PE connection to EN 61800−5−1.

– Tighten the cable gland

0.

For shielded cables: Securely connect the shield to the cable gland with a surface
as large as possible.

– Connect cores and shield to the basic device observing the documentation for the

basic device.

4. Connect the thermal contact cables:

– Use a twisted cable.
– Pass the cable through the cable gland

1.

– Connect the cores to connections T1 and T2 of the brake resistor observing the

tightening torque.

– Tighten the cable gland

1.

– When integrating the thermal contact into the system monitoring ensure that the

mains supply will be switched off when the brake resistor is overheated.

5. Mount the terminal cover.