MTS Series 505G2 SilentFlo Hydraulic Power Unit Model 505G2-11 User Manual

Page 32

Advertising
background image

Model 505G2.07/.11 SilentFlo™ HPU

32

HPU Setup

5. The following table describes the pushbuttons and indicators on the Setup

screen.

Name and Location

Description

Use Buttons Below To Change
Parameters

Indicator - blue-green: Provides instruction for the setup screen.

Remote Fault Normal/Remote Fault
Reverse

Pushbutton /Indicator. The HPU generates fault signals for remote
monitoring. This button is used to define the polarity of the output

signal.

Remote Fault Normal - gray: The remote fault signal is active high

meaning the fault contact is closed when a fault is present.

Remote Fault Normal - black: The remote fault signal is active

low meaning the fault contact is open when a fault is present.

Aux Contact: On/Off/Temp
Aux Polarity Normal/Reverse

Pushbuttons /Indicators.

Aux Contact: On/Off - gray

Aux Contact: Temp - black

Aux Polarity Normal - gray

Aux Polarity Reverse - black

One of the auxiliary contacts can be used to control an external

device such as a warning lamp or a remote cooling circuit. The

auxiliary contact controls whether the contact is active whenever a
pump motor is running (Aux Contact: On/Off - gray) or

whenever a pump motor is running and the temperature of the

hydraulic fluid in the reservoir reached the trip temperature (Aux
Contact: Temp
- black).

Press the Aux Contact: button to display Aux Contact:
On/Off
to activate the contact when at least one pump
motor is running, and to deactivate when no pump
motors are running.

Press the Aux Contact: button to display Aux Contact:
Temp
to activate the contact when at least one pump
motor is running and the fluid temperature in the
reservoir is above the temperature trip level and to
deactivate the contact when either the temperature is
lower than the temperature trip level or no pump motors
are running.

Press the Aux Polarity: button to display Aux Polarity:
Normal
to cause the contact to close when it is active.
MTS Controllers use normal polarity.

Press the Aux Polarity: button to display Aux Polarity:
Reverse
to cause the contact to open when it is active.

The other Aux contact is set for motor pump running only. Its

function and polarity are not selectable.