BATTERY (gA6hRs)

This unit is of negative ground

dO NOT connect in reverse.

Always maintain battery fluid level between the specified

marks. Battery life will be shortened, if the fluid levels are

not properly maintained. Add only distilled water when

replenishment is necessary.
Check to see whether the battery cables are loose. Poor

contact may result in poor starting or malfunctions. Always

keep the terminals firmly tightened. Coating the terminals

with an approved battery terminal treatment compound

will help prevent corrosion. Replace battery with only

recommended type battery.
The battery is sufficiently charged if the specific gravity

of the battery fluid is 1.28 (at 68° F). If the specific gravity

should fall to 1.245 or lower, it indicates that the battery is

dead and needs to be recharged or replaced.
Before charging the battery with an external electric source,

be sure to disconnect the battery cables.

BATTERY CABlE iNsTAllATiON

AlWAYs be sure the battery cables are properly connected

to the battery terminals (Figure 38). The

red cable is

connected to the positive terminal of the battery, and the

black cable is connected to the negative terminal of the

battery.

Figure 38. Battery Connections

NOTICE

Inadequate battery cable connections may cause poor

starting of the generator, and create other malfunctions.

POSITIVE

NEGATIVE

mAINTENANCE

When connecting battery do the following:
1.

NEvER use worn or damaged battery cables. Replace

defective battery cables immediately.

2. Place a small amount of battery terminal treatment

compound around both battery terminals. This will

ensure a good connection and will help prevent

corrosion around the battery terminals.

pOlARiTY

The polarity of the battery is extremely important. When an

inverted circuit connection takes place, the circuit will be in

short circuit instantaneously resulting in possible damage

to the control box electronics and starter.
When connecting the battery cables to the battery terminals

be sure to check the polarity.

TEsTiNg ThE gFCi mOdulE

If tripping of the

main circuit breaker persists after a load is

replaced with a known good one (no short circuit), perform

this test with no load.
1. Start the generator as outlined in the start up procedure

in this manual.

2. Place the main circuit breaker (Figure 39) in the

ON

position.

Figure 39. Circuit Breaker ON (GFCI Test)

NOTICE

AlWAYs disconnect the negative terminal first and

reconnect negative terminal last.

NOTICE

If the battery cables are connected incorrectly, electrical

damage to the generator will occur. Pay close attention

to the polarity markings on the battery when connecting

the battery cables.