M2 Transmitter Operator’s Manual, 12 VDC Operation

34

Register 3

Register 3 is the supply voltage (0.1 volt per count).

Registers 4 - 11

The 16 bytes in these registers contain the same ASCII text information that is displayed
on the M2’s LCD (not NULL terminated).

[11]

Gas Type Change
0=Not Changed
1=Changed

[10]

Configuration Change
0=Not Changed
1=Changed

[9]

Calibration Activity Flag
0=No Calibration Activity
1=Calibration Activity Has Occurred

[8]

Fail Status
0 = Fail Not Asserted
1 = Fail Asserted

[7:6]

Alarm 2 Status
0 = No Alarm
1 = Unacknowledged Alarm
2 = Acknowledged Alarm
3 = Unused Code

[5:4]

Alarm 1 Status
0 = No Alarm
1 = Unacknowledged Alarm
2 = Acknowledged Alarm
3 = Unused Code

[3]

Overscale Status
0=Not Overscale
1=Overscale

[2]

Fail Relay Status
0 = Not Energized
1 = Energized

[1]

Alarm 2 Relay Status
0 = Not Energized
1 = Energized

[0]

Alarm 1 Relay Status
0 = Not Energized
1 = Energized

Table 11: Register 2, Operating State, Alarms & Relays Bit & Field Assignments (Continued)