8 • Installation

Model GD-K11D Operator’s Manual

Installation

This section describes how to install the Model GD-K11D at the monitoring site. This
section includes procedures to mount the Model GD-K11D, connect sample lines to the
Model GD-K11D, and make power and other wiring connections to the Model GD-K11D.

Mounting the Model GD-K11D

CAUTION:

The Model GD-K11D is suitable for installation in indoor areas where general

purpose equipment is in use.

1. Select a mounting site that is representative of the monitoring environment. Consider

the following when you select the mounting site.

Select a site where the Model GD-K11D is not likely to be bumped or disturbed.
Make sure there is sufficient room to make wiring and sample line connections at
the bottom of the transmitter. Also make sure there is sufficient room to open the
housing cover and perform start-up, maintenance, and calibration procedures.

Select a site near the sampling area.

NOTE:

If your application does not require a specific mounting site, mount the

transmitter at approximately eye level.

Figure 2: Mounting the Model GD-K11D

GAS DETECTOR

MODEL

GD-K11D

Note 1: All measurements in inches.

7.3

8.2

7.3

8.4

9.1

9.8

1.2

.45

.48

Note 2: Model GD-K11D is 4.1 inches deep.

Note 3: Allow at least 2 feet in front of

Model GD-K11D to open housing door.

0.3 dia.

(4 times)