16 • Alarms

Model GD-K11D Operator’s Manual

Alarms

This section describes the Model GD-K11D’s visual indications for normal, alarm, and fail
conditions. This section also suggests response to these conditions.

Alarm Indications

Table 5 lists the indications for normal, alarm and fail conditions.

The Model GD-K11D includes an alarm delay feature. The alarm indications listed below
are delayed by 3 seconds once the Model GD-K11D recognizes an alarm or fail condition.

Responding to Alarms

This section suggests response to gas and fail alarms.

Responding to gas alarms

1. Follow your established procedure for an increasing toxic gas condition.

2. When the display reading falls below the alarm point, the alarm circuit automatically

resets itself. The AL (alarm) light turns off.

Responding to fail alarms

1. Set the correct flow rate with the flow adjust valve.

2. If you cannot set the correct flow rate, check the sample lines for obstructions or kinks.

3. Calibrate the Model GD-K11D as described on page 21.

4. If the fail condition continues, replace the sensor as described on page 18.

5. If the fail condition continues, contact RKI Instruments, Inc., for further instruction.

Table 7: Model GD-K11D Alarm Indications

Condition

Cause(s)

Indications

Alarm Contacts

Normal

• Start up complete
• No gas or fail alarms

PW/TR light

De-energized

Gas

Alarm

Increasing gas reading at
or above alarm point

AL light

Energized

Fail

Alarm

Disconnected sensor

E-01 on screen

PW/TR light

1

AL light
• 0.5 mA output

De-energized

Low Flow

Alarm

Low flow rate

E-05 on screen

PW/TR light

1

• Low flow (red) light

on main board

• 0.5 mA output

De-energized

1

The PW/TR (power) light flashes.