19. TROUBLE SHOOTING GUIDE for Honeywell S87J-1034 Ignition Control

SET THERMOSTAT TO CALL FOR HEAT

RELAY CLOSES

COMBUSTION AIR BLOWER STARTS

AIR PROVING SWITCH CLOSED.
24 VOLTS AT IGNITION CONTROL

SPARK ACROSS IGNITER OR
IGNITER/SENSOR GAP

CHECK THERMOSTAT

CHECK FOR LINE VOLTAGE POWER SUPPLY

CHECK WIRING CONNECTION AND RE-
PLACE BLOWER MOTOR IF DEFFECTIVE

ENSURE THAT THE AIR INTAKE AND FLUE
ARE NOT BLOCKED
ENSURE PRESSURE TUBE IS CONNECTED
AND NOT BLOCKED
CHECK AIR PRESSURE WITH MANOMETER
CHECK AIR PROVING SWITCH IS CLOSING
WHEN BLOWER IS RUNNING
REPLACE DEFECTIVE SWITCHES

PLEASE SEE APPENDIX 1 SPARK IGNITION
CIRCUIT
PULL IGNITION LEAD AND CHECK SPARK
SPARK OK?

REPLACE IGNITION CONTROL

CHECK IGNITION CABLE, GROUND WIRING
CERAMIC INSULATOR AND CAP, AND
CORRECT
CHECK BOOT OF THE IGNITION CABLE FOR
SIGNS OF MELTING OR BUCKLING
TAKE PROTECTIVE ACTION TO SHIELD CA
BLE AND BOOT FROM EXCESSIVE TEM
PERATURES

YES

YES

YES

NO

NO

NO

YES

NO

NO

YES