SP-MSTR-AC-11A

STR Manual

RD: NOV, 2003

RL: 11

KH

CHECK FOR PROPER TEMPERATURE
CONTROLLER OPERATIONS

REMOVE VALVE LEAD AT IGNITION

CONTROL, IF VALVE CLOSES, RECHECK
TEMPERATURE CONTROLLER AND WIR
ING, IF NOT, REPLACE GAS CONTROL.OR

CALL FOR HEAT ENDS:
SYSTEM SHUTS OFF

YES

NO

MAIN BURNER LIGHTS

CHECK FOR 25 VAC ACROSS VALVE AND
VALVE TERMINALS IN IGNITER AND CAP, IF
NO VOLTAGE, REPLACE IGNITION CON-
TROL

SPARK IGNITER MAY BE OUT OF POSITION

CHECK ELECTRICAL CONNECTION BE
TWEEN IGNITION CONTROL AND GAS CON
TROL, IF OKAY, REPLACE GAS CONTROL

YES

NO

SPARK STOPS WHEN
BURNER LIGHTS

SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS

YES

NO

YES

NO

NOTE: IF IGNITION CONTROL GOES INTO
LOCKOUT, RESET SYSTEM

CHECK CONTINUITY OF SENSOR CABLE
AND GROUND WIRE

CHECK THAT BURNER FLAME COVERS
ALL ELECTRODES

IF CHECKS ARE OKAY, REPLACE IGNITION
CONTROL

NOTE: IF IGNITION CONTROL GOES INTO

LOCKOUT, RESET SYSTEM

CHECK CONTINUITY OF SENSOR CABLE
AND GROUND WIRE

NOTE: IF GROUND IS POOR OR ERRATIC,

SHUTDOWNS MAY OCCUR OCCASIONALLY,
EVEN THOUGH OPERATION IS NORMAL AT
THE TIME OF CHECKOUT IF CHECKS ARE
OKAY, REPACE IGNITION CONTROL

TROUBLESHOOTING ENDS