no combustibles on face of unit.
combustibles May not extend to

unit face.
do not notch wallboard around

standoffs.

installation

The FP90 may be placed on or near construction

materials. The combustion air kit, fire stop spacer

and roof flashings (not chase flashings) may be

placed directly on or against normal construction

materials. The chimney requires a minimum 2"

(51mm) clearance. A combustible mantle (to a

depth of 10", 254mm) may be installed no closer

than 18" (457mm) above the warm air vent or

55-1/2" (1410mm) from bottom of unit.

The chimney must be enclosed when installed

in or passing through a living area where

combustible material or people may come in

contact with it. This is important to prevent

possible personal injury or fire hazard.

For any further information, please call your

dealer. Special restrictions apply to the front and

facing of the fireplace and nearby walls.

WarninG: If insulation is used, do not place

the unit against it. Insulation or vapor barriers,

if used, must be secured to assure insulation

and vapor barriers remain in place and do not

affect the required air spaces.

WarninG: Do not pack or fill required air spaces

with insulation or other material. No material of

any kind is allowed in these areas.

notes:

1) Do not insulate the chase cavity with blown

or fill type insulation materials.

2) Local codes may not require firestopping

at the ceiling level for outside chase

installations; however, it is recommended

for safety and the reduction of heat loss.

3) We recommend that you insulate at least

the first floor of the chase to prevent heat

loss.

4) Some local codes require 1 hour fire rating

on one or all sides of fire chases. Check

with your local authorities.

clearances and HeiGHt reQuireMents

Clearances to Combustibles

Max. 10" (254mm)

Depth of Mantel

center line

18" (457mm)

55-1/2" (1410mm)

from bottom of unit

2"

(51mm)

Mantel leg can

go in this

area

5"

(127mm)

40" (1016mm)

20" (508mm)

18" (457mm)

note for Mantel leGs:

For every 1" (25mm) pretrusion

greater than 5" (127mm), you

must travel away from the unit

1" (25mm) starting at 2" (51mm)

from the edge of the hearth

extension.