Change basic settings - level 2 – Waldmann PULSE HFMD version VFC III - with MFT User Manual

Page 14

Advertising
background image

14

GB

Operating Manual Light control “PULSE HFMD - Vers. III“

GB

Operating Manual Light control “PULSE HFMD - Vers. III“

LED 1 2 3 4 5 6

Fig. 6

Change basic settings - Level 2

Activate setting level 2 (function 20)

Logo is off

Sensor LEDs fl ash green

Actuation

Display

Press both keys

until the logo switches

from fl ashing

to OFF

Change function

Increase the follow-up time in stages

Briefl y press key I

The light bar shows the newly

set follow-up time.

Each LED which does not fl ash

means a follow-up time of 5 min:

- Level 1 LED 1

5 min

- Level 2 LED 1-2

10 min

- Level 3 LED 1-3

15 min

- Level 4 LED 1-4

20 min

- Level 5 LED 1-5

25 min

- Level 6 LED 1-6

30 min

Change function

Reduce follow-up time in stages

Briefl y press key II

The light bar shows the newly

set follow-up time.

Fig. 3

Key I

Logo

Light

bar
Key II

LED I

LED II