Rockwell Automation 20P PowerFlex DC Drive - Frame C Switching Power Supply Circuit Board Fuses User Manual

Page 5

Advertising
background image

PowerFlex® DC Drive - Frame C Switching Power Supply Circuit Board Fuse Replacement

5

10. Insert the new fuses into the appropriate holders and replace the fuse

holder caps.

Important: For drives with Switching Power Supply circuit board SW3-32,

rev. H & below, insert the 3.15A 250V fuse in the fuse holder
designated F1. Insert the 2.5A 250V fuse in the fuse holder
designated F2.

11. Lift the EMI Shield, connect the cable to connector XSW on the

Switching Power Supply board and secure the EMI Shield with the two
captive screws.

12. Connect the cables to connectors XFCD and XR on the Control board.

13. Connect the Communication cable from the HIM on the top Protective

Cover to the connector on the upper right corner of the Control board
and install the Protective Covers in the reverse order of removal.

14. Connect the DPI cable to the HIM (if present).

F1 = 3.15A
250V fuse

F2 = 2.5A
250V fuse

Advertising