Step 4: remove the existing bimetal thermostat – Rockwell Automation 20P PowerFlex DC Drive - Frame B Bimetal Thermostat User Manual

Page 10

Advertising
background image

10

PowerFlex® DC Drive - Frame B Bimetal Thermostat

12. Remove the seven screws that secure the board to the stand-offs on the

drive chassis and remove the boards from the drive.

Step 4: Remove the
Existing Bimetal Thermostat

1. Remove the appropriate bus bars in order to access the Bimetal

Thermostat.

If removing the bus bars from a Regenerative drive, refer to

Remove

the Bus Bars from a Regenerative Drive on page 11

.

If removing the bus bars from a Non-Regenerative drive, refer to

Remove the Bus Bars from a Non-Regenerative Drive on page 13

.

Remove screws

Note: Regenerative Drive Shown