PowerFlex® DC Drive - Frame B Bimetal Thermostat

13

Remove the Bus Bars from a Non-Regenerative Drive

2. Remove the three bolts and washers that secure the U Phase and D

power terminals to the isolation bar.

3. Remove the bolts and washers that secure the wires and bus bars to the

U phase SCR Module and D power terminal and remove the bus bars.

Continue with

Remove the Bimetal Thermostat on page 14

.

=

Remove bolts, washers and wires

Non-Regenerative Drive

U Phase Terminal

D Terminal

Non-Regenerative Drive

Remove bolts, washers and wires