13. Turn the Pulse Transformer board over and remove the cables from

connectors XV and XUV on the Switching Power Supply board.

14. Remove the six screws that secure the Switching Power Supply board to the

stand-offs on the back of the Pulse Transformer board and remove the
Switching Power Supply board.

15. Remove the six stand-offs and washers from the back of the Pulse

Transformer board. Retain stand-offs and washers for reuse.

Step 4: Configure the New

Pulse Transformer
Board

The Pulse Transformer circuit board must be configured to match the drive size
(armature output current and HP rating). The steps required to complete the
configuration are different based on the revision code of the board. See either,

Pulse Transformer Board FIR2-XX Rev. “M” and Lower

below, or

Pulse

Transformer Board FIR2-XX Rev. “N” and Higher on page 16

.