Rockwell Automation 20P PowerFlex DC Drive - Frame B Pulse Transformer Circuit Board User Manual

Page 17

Advertising
background image

Rockwell Automation Publication 20P-IN009D-EN-P - February 2012

17

PowerFlex DC Drive Frame B Pulse Transformer Circuit Board

Table 7 - 575V AC Input Drives

Step 5: Install the New

Pulse Transformer
Board and Existing
Switching Power
Supply Board

1. Install the new Pulse Transformer board and existing Switching Power

Supply board in reverse order of removal.

2. Replace the cables connected to connector X3, X4, XP and XR on the

Pulse Transformer board and the gate lead cables with the new cables
provided.

3. Verify that the four plastic board stabilizers mounted on the top air flow

plate are placed one on either side of each of the Pulse Transformer and
Switching Power Supply boards.

Drive

Current

Rating

Code

DC

Amps

AC Line

Amps

HP

DIP Switch S3

DIP Switch S4

S3-1

S3-2

S3-3

S3-4

S3-5

S3-6

S3-7

S3-8

S4-1

S4-2

S4-3

S4-4

S4-5

S4-6

S4-7

S4-8

67

67

55.1

50

ON

ON

ON

ON

101

101

82.7

75

ON

ON

ON

ON

135

135

110.3

100

ON

ON

ON

ON

270

270

220.6

200

ON

ON

ON

ON

405

405

330.9

300

ON

ON

ON

ON

ATTENTION: Each gate lead cable must be connected to the exact connector
from which it was removed on the Pulse Transformer circuit board or damage to
the drive may occur.

One plastic stabilizer should be on either side of each board

Air flow plate

Plastic
stabilizers

Top view of Pulse Transformer board

Side cut-away view

Pulse Transformer board

Switching Power Supply board