PowerFlex® DC Drive - Frame C AC Line Snubber Board and High Wattage Resistors
9
2. Remove the appropriate gate leads:
– For non-regenerative drives, remove each pair of (orange and yellow)
gate lead cables from connectors KG1 - KG6 and push each lead
through the appropriate opening in the board.
– For regenerative drive, remove each pair of (orange and yellow) gate
lead cables from connectors KG01 - KG06 and KG1 - KG6 and push
each lead through the appropriate opening in the board.
Important: Carefully remove the gate leads by grasping the connector.
DO NOT pull the gate leads off by pulling on the wires.
3. Remove the cable from connector XTA on the Pulse Transformer board
(see
for location).
=
Remove cable
Remove gate
leads
Regenerative Drive
Non-Regenerative Drive
Remove cable
Remove gate
leads