Step 7: install the new filter capacitor assembly – Rockwell Automation SK-L1-CAP2-D1250 Filter Capacitor Kit SK-L1-CAP2-D1250 for PowerFlex 700L Fr. 3B 480V AC Drives User Manual

Page 10

Advertising
background image

10

Rockwell Automation Publication 20L-IN016A-EN-P - February 2012

Filter Capacitor Replacement Kit SK-L1-CAP2-D1250 for PowerFlex 700L Frame 3B 480V AC Drives

Step 7: Install the New

Filter Capacitor
Assembly

a. Before installing the new capacitor bank assembly, attach the power

wires to the back of the capacitor bank assembly using the hardware
removed in Step 5-i (see

Figure 6

). Connect Rockwell Automation

power wire PN-109106 to the Bus Bar labeled FU-4, Rockwell
Automation power wire PN-109107 to the Bus Bar labeled FU-5, and
the remaining Rockwell Automation power wire PN-109107 to the Bus
Bar labeled FU-6. Tighten to 45…50 lb•in (5.1…5.6 N•m).

b. Place the new capacitor bank assembly in the enclosure and hang it

from the three (3) studs on the upper capacitor bank mounting bracket
(see

Figure 7

).

c. Using three (3) M6 hex nuts (supplied with kit), secure the top of the

capacitor bank assembly in place. Tighten only to finger-tight until the
remaining hardware is in place (see

Figure 7

).

d. Secure the bottom of the capacitor bank assembly with three (3) bolts

removed from Step 5-i (see

Figure 7

).

e. Tighten all hardware installed in Step 7-c and Step 7-d.
f. Using access from the left side and the hardware removed in Step 5-e,

secure the power wire coming from FU-6 to the right hand inductor
connection, the power wire coming from FU-5 to the center inductor
connection, and the power wire coming from FU-4 to the left hand
inductor connection (see

Figure 6

). Tighten to 30…35 lb•ft

(40.7…47.5 N•m).

g. Connect the free lead from the 1 μF Capacitor to the terminal on the

capacitor bank assembly.

h. Insure that the surge trap style SPD, shown in the “Precheck”

section on

page 3

, is installed and reconnected properly.

Figure 6 - Power Wire Connections

ATTENTION: Upon installing the assembly and hardware, sharp edges may be
encountered. Use work gloves to protect your hands.

Rockwell PN-109107
Power Wire to FU6

Bleeder Resistor Harness

Rockwell PN-109107
Power Wire to FU5

Rockwell PN-109106
Power Wire to FU4

Resistor Mounting Hardware
(12x) M3 x 8 pan head screws

Advertising