Figure 2 - Existing Filter Capacitor Assembly in Drive

Step 5: Remove the

Existing Filter
Capacitor Assembly

a. After power has been removed from the drive, the filter capacitor bank

should discharge via the bleeder resistor discharge network. Wait five
(5) minutes to fully discharge.

b. Carefully check for zero (0) volts between each of the three (3)

Capacitor Bus Bars (input power) and the Neutral Bus Plate at the
stake-on connectors (see

Figure 1

) using a confidence-tested DC

voltmeter.

c. Gain access to the left side of the enclosure. Remove and retain the

hardware that secures the left side panel to the enclosure, and remove
the panel and set it aside.

d. Cover any components under the capacitor bank to protect them from

any dropped hardware.

e. Place a piece of rigid cardboard or something similar on top of the three

(3) Bus Bars connected to the contactors to prevent any damage to the
Bus Bars (see

Figure 3

) or their protective coating.

1 μF Capacitor

Power Wires (3x)
(not shown)

Mounting Hardware (4x)

Harness for Bleeder
Resisitor network

Fiberglass Insulator Panel

Capacitor Bank
Mounting Hardware (6x)

Panel Mounting
Hardware (6x)

Capacitor Bus Bars (3x)
Input Power

ATTENTION: Upon removing the assembly and hardware, sharp edges may be
encountered. Use work gloves to protect your hands.