Tools That You Need

Properly-rated, isolated multi-meter (DMM) to measure the AC input
and DC filter capacitor voltages (working voltage specifications should be
1000V)

3/8-inch drive ratchet

3/8-inch drive 10 mm deep well socket

3/8-inch drive 3/4-inch deep well socket

3/8-inch drive 3/8-inch socket or 3/8-inch box wrench

Torque wrench capable of 50 lb•in (5.6 N•m)

Torque wrench capable of 35 lb•ft (47.5 N•m)

10 mm box wrench

T25 Torx bit

#1 Phillips screwdriver

Small wire cutter

Lockout/Tagout kit

Work gloves

Nylon wire ties

Arc Flash Gear

You may also need a box or container to hold loose hardware.

Precheck

Drives built prior to May 2008 had older style SPDs mounted on the filter
capacitor bank assemblies. If a surge trap style SPD is not installed in the drive, it
is necessary to order and install a surge trap upgrade kit, Catalog Number 21T-
385253-A01 to insure there is proper transient protection for the equipment.

IMPORTANT

Inspect the surge trap (SPD) in the drive and note whether the visual
inspection tab has been activated. This indicates internal damage and the need
for replacement. For the location of the surge trap, see

Figure 7 on page 11

.