Rockwell Automation 440C-CR30-22BBB Guardmaster Software Configurable Safety Relay Quick Start Guide User Manual
Page 31
Rockwell Automation Publication 440C-QS001A-EN-P — January 2014
29
Quick Start Guide
3.
Add the multi-state indicators for the faults.
4.
Press the reset button to get the outputs on.
Create a short-circuit from terminal 0 to terminal 1.
5.
The PanelView C600 will look like this.
Crossfault 12 – a crossfault occurred on terminal 12, which is Input Test Pulse A.
E-STOP OFF – since Input Test Pulse A is used by the e-stop SMF, it turns OFF.
Gate OFF – since Input Test Pulse A is also used by the Gate SMF, it turns OFF.
The fault causes the Output to turn OFF.
Bit 0 for e-stop provides the message on the “At least one circuit shorted to 24V
or another input circuit” when the mouse is moved over the e-stop or Gate SMF
on the CCW.
Remove the short circuit and cycle the e-stop and gate switch. The Guardmaster
440C-CR30 is now ready for the reset button.