Troubleshooting steps, Table 17 - troubleshooting steps – Rockwell Automation 150-E SMC Elevator Users Manual User Manual

Page 25

Advertising
background image

Rockwell Automation Publication150-UM0009D-EN-P - February 2011

25

Troubleshooting Chapter 4

Troubleshooting Steps

Table 17 - Troubleshooting Steps

Control

Device Status

Solution

Prestart - no start command given but device is faulted.

LED Flashing

Reset fault.
Allow device to cool (overload or SCR over temp). Reset fault.
Cycle power to device.

Motor fails to start after start command given.

LED Off

Check control power.
Check control circuit connections.

LED ON

Verify proper operation of fault contactor or isolation devices.
Check connections to the motor.
Verify line power and frequency are within specifications.

LED Flashing

Reference the LED Fault Indication & Diagnostics Table for information

related to specific fault codes.

Motor attempts to start after start command is given,
but fails to reach an up-to-speed condition.

LED ON

Verify proper operation of the fault contactor or isolation devices.
Verify line power and frequency are within specifications.
Try increasing the initial torque or current limit setting.

LED Flashing

Reference the LED Fault Indication & Diagnostics Table for information

related to specific fault codes.

Motor stops abruptly and fails to restart.

LED Off

Check for a blown fuse or tripped circuit breaker.
Ensure the control power and start command are present.
Verify proper operation of the fault contactor or isolation devices.

LED ON

Verify proper operation of the fault contactor or isolation devices.

LED Flashing

Reference the LED Fault Indication & Diagnostics Table for information

related to specific fault codes.

Fault contactor fails to close when power is applied.

All Conditions

Verify wiring to the coil. The contactor should close when power is

applied to the controller.

Verify voltage across the coil (A1 to A2).
Check the resistance of the coil. Replace, if measured open.
Verify internal contact of the controller (terminals 97/98) are properly

changing state. Replace the controller if the contact does not operate
correctly.