Troubleshooting Chapter 4

Troubleshooting Steps

Table 17 - Troubleshooting Steps

Control

Device Status

Solution

Prestart - no start command given but device is faulted.

LED Flashing

• Reset fault.
• Allow device to cool (overload or SCR over temp). Reset fault.
• Cycle power to device.

Motor fails to start after start command given.

LED Off

• Check control power.
• Check control circuit connections.

LED ON

• Verify proper operation of fault contactor or isolation devices.
• Check connections to the motor.
• Verify line power and frequency are within specifications.

LED Flashing

• Reference the LED Fault Indication & Diagnostics Table for information

related to specific fault codes.

Motor attempts to start after start command is given,
but fails to reach an up-to-speed condition.

LED ON

• Verify proper operation of the fault contactor or isolation devices.
• Verify line power and frequency are within specifications.
• Try increasing the initial torque or current limit setting.

LED Flashing

• Reference the LED Fault Indication & Diagnostics Table for information

related to specific fault codes.

Motor stops abruptly and fails to restart.

LED Off

• Check for a blown fuse or tripped circuit breaker.
• Ensure the control power and start command are present.
• Verify proper operation of the fault contactor or isolation devices.

LED ON

• Verify proper operation of the fault contactor or isolation devices.

LED Flashing

• Reference the LED Fault Indication & Diagnostics Table for information

related to specific fault codes.

Fault contactor fails to close when power is applied.

All Conditions

• Verify wiring to the coil. The contactor should close when power is

applied to the controller.

• Verify voltage across the coil (A1 to A2).
• Check the resistance of the coil. Replace, if measured open.
• Verify internal contact of the controller (terminals 97/98) are properly

changing state. Replace the controller if the contact does not operate
correctly.