Table 20 - Control Circuit
Table 21 - Short Circuit Capabilities
UL/cUL/CSA
IEC
Rated Operational Voltage 100...120V AC, 200...240V AC
120~, 240~
Rated Insulation Voltage —
300V~
Di-electric Withstand —
3000V
Rated Impulse Voltage
3 kV
Operating Frequency
50/60 Hz
Control Power Requirements 32/52/64
215 mA @ 120 V AC ,
180 mA @ 240 V AC
74/104/147
200 mA @ 120 V AC ,
100 mA @ 240 V AC
234
200 mA @ 120 V AC ,
120 mA @ 240 V AC
Fan Power Requrements 32/52/64
—
74/104/147
—
234
20VA
Short Circuit Performance
Type 1
Device Current Rating Maximum Fuse Size & Type
Maximum Available Fault
Rating
32
70 A - RK5
5 kA
125 A - K5
5 kA
51
125 A - RK5
5 kA
200 A - K5
10 kA
64
125 A - RK5
5 kA
200 A - K5
10 kA
74
150 A - RK5
5 kA
250 A - J
10 kA
104
200 A - RK5
5 kA
400 A - J
10 kA
147
250 A - RK5
10 kA
400 A - J
10 kA
234
400 A - RK5
10 kA
450 A - K5
10 kA