Drive rear bus-bar kit installation – Rockwell Automation 20G PowerFlex 750-Series Power Option Cabinets User Manual
Page 26

26
Rockwell Automation Publication 750-IN030B-EN-P - October 2014
PowerFlex 750-Series Power Option Cabinets
Drive Rear Bus-bar Kit
Installation
Drive rear bus-bar kits provide an AC and DC line input power and AC motor
connection point behind the drive’s extruded bus-bar.
Reuse the drive’s L-brackets.
Table 22 - 20-750-PBAY-RBRK-2 Kit Contents
1. Assemble the M10 carriage bolts and clamp plates.
2. Slide the bolt assemblies into the cannel of the drive’s extruded bus-bar.
3. Align the four bolts on the drive rear bus-bar.
4. Tighten M10 nuts to 38.0 N•m (336 lb•in).
Description
Part No.
Quantity
Drive Rear Bus-bar
–
1
M10 x 45 mm Carriage Bolt
29220-903-02
4
Bus-bar Clamp Plate
PN-37764
4
M10 Nut with Washer
29355-002-01
4
IMPORTANT
Verify that clamp fits squarely in the bus-bar slot.