Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 284
Advertising

284
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 8 EtherNet/IP Communications
The New Entry window appears with the module's Ethernet Address (MAC).
6.
Type the IP address, host name, and a module description.
7.
Click OK.
8.
Cycle power to the E300 Electronic Overload Relay EtherNet/IP
Communication Module.
9.
To permanently assign this configuration to the module: Select the
module in the Relation List panel and click Disable BOOTP/DHCP.
When module power is cycled, it uses the assigned configuration and does not
issue a DHCP request.
If you do not click Disable BOOTP/DHCP, on a power cycle, the module clears
the current IP configuration and will again begin sending DHCP requests.