SensaGuard™ 18 mm Plastic Barrel Unique Coding

3

Rockwell Automation 440N-IN013A-EN-P—October 2014

18 mm Unit with 30 mm Target

Wiring Diagram

8-Pin Unit

Recommended mating cable, 2 m (6.5 ft)—889D-F8AB-2.
Replace the 2 with 5 (5 m) or 10 (10 m) for standard cable lengths.

There must be a minimum spacing of 7 mm
(0.275 in.) if actuator and sensor face approaches
laterally. This will prevent false triggering due to
the side lobe areas.

Pin Number

Wire Color

Signal

1

White

Aux. Outputs

2

Brown

+24V

3

Green

NA

4

Yellow

OSSD 2, +24V Input

5

Grey

OSSD 1

6

Pink

OSSD 2

7

Blue

0V

8

Red

OSSD 1, +24V Input

0

5

10

15

20

25

30

35

-30

(-1.18)

-20

(-0.787)

-10

(-0.39)

0

10

(0.39)

20

(0.787)

30

(1.18)

Face to Face Distance—mm

Side Lobe

Side Lobe

Assured Sensing

Distance

OFF

OFF

ON

Lateral Misalignment Tolerance—mm (in)

Assured Sensing

Distance

OFF

IMPORTANT

4

7

6

8

1

5

2

3

Brown

White

Blue

Pink

Grey

Green

Red

Yellow

5-Pin Unit

Recommended cordset, 2m (6.5 ft) - 889D-F5AC-2. Replace the
2 with 5 (5 m) or 10 (10 m) for standard cable lengths.

Note: If the user does not require the Auxiliary signal, a 4-pin
cordset (889D-F4AC-2) can be used.

Recommended patchcord for use with ArmorBlock® Guard
Safety I/O, 2 m (6.5 ft) - 889D-F4ACDM-2.
Replace the 2 with
0M3 (0.3 m), 1 (1 m), 5 (5 m), or 10 (10 m) for standard cable
lengths.

Note: Do not use a 5-pin patchcord with the ArmorBlock.

Diagnostic

Unit Indicators (per IEC 60073)

Pin Number

Signal

1

+24V

2

OSSD 1

3

0V

4

OSSD 2

5

Aux.

Device

Output

LED

State

Status

Troubleshooting

Off

Not Powered

NA

Red

Not Safe, OSSD not active

NA

Green

Safe, OSSD active

NA

Green

Flash

Power up test or OSSD inputs

not valid

Check 24V DC or OSSD inputs

(yellow and red wire)

Red

Flash

1 Hz Flash Recoverable Fault

4 Hz Flash Non-recoverable Fault

Recoverable fault —check

OSSD outputs are not shorted
to GND, 24V DC or each other.

Cycle power.

Refer to Technical Specifications (page 1) for
certification information and ratings.

1

5

2

4

3

IMPORTANT