Rockwell Automation 500LG Lighting Contactor Instruction Manual User Manual
Page 10

Installing Bulletin 500LC Lighting Contactors
10
Publication 500LC–IN001A–EN–P May 2005
For DC modules be sure to connect
terminal 4 to negative (–).
Table G – Connections to Solid–State Control Modules
Module Terminal
Connected To
1
not used
2
control station for Mod. 500LC–48CM*, 500LC–49SS*
3
control station for Mod. 500LC–47CM*,
500LC–48SS*, 500LC–49SS*
4
Control Module control voltage*
5
500LC Lighting Contactor control voltage
O
pre–connected to O on 500LC Lighting Contactor
C
pre–connected to C on 500LC Lighting Contactor
3 WIRE CONTROL
MOD. 500LC–48CM*
2 WIRE CONTROL
MOD. 500LC–47CM*
START–STOP
(FORM 3) CONTROL
MOD. 500LC–49SS*
Figure 1 Typical labels on control modules
Table H – Ratings for Control Modules
Nominal Input Voltage see Table F, AC voltages are 50/60 Hz
.
Control Voltage Range
80...125% of nominal
. . . . . . . . . . . . . .
Ambient Temperature Range Operate
0˚...+45˚C
. . . . . . . . . .
Ambient Temperature Range Storage
–30˚...+65˚C
. . . . . . . . .
Control Module
Mod.
500LC–47CM*
Mod.
500LC–48CM*
Mod.
500LC–49SS*
Control Module
AC
DC
AC
DC
AC
DC
120V AC
1.90
—
1.60
—
3.70
—
24V AC & DC
0.85
0.36
0.34
0.38
0.70
0.72
240 / 277V AC
4.00
—
2.50
—
6.00
—
12V AC & DC
0.60
0.32
0.34
0.36
0.68
0.70