Rockwell Automation 500LG Lighting Contactor Instruction Manual User Manual

Page 10

Advertising
background image

Installing Bulletin 500LC Lighting Contactors

10

Publication 500LC–IN001A–EN–P May 2005

For DC modules be sure to connect

terminal 4 to negative (–).

Table G – Connections to Solid–State Control Modules

Module Terminal

Connected To

1

not used

2

control station for Mod. 500LC–48CM*, 500LC–49SS*

3

control station for Mod. 500LC–47CM*,

500LC–48SS*, 500LC–49SS*

4

Control Module control voltage*

5

500LC Lighting Contactor control voltage

O

pre–connected to O on 500LC Lighting Contactor

C

pre–connected to C on 500LC Lighting Contactor

3 WIRE CONTROL

MOD. 500LC–48CM*

2 WIRE CONTROL

MOD. 500LC–47CM*

START–STOP

(FORM 3) CONTROL

MOD. 500LC–49SS*

Figure 1 Typical labels on control modules

Table H – Ratings for Control Modules
Nominal Input Voltage see Table F, AC voltages are 50/60 Hz

.

Control Voltage Range

80...125% of nominal

. . . . . . . . . . . . . .

Ambient Temperature Range Operate

0˚...+45˚C

. . . . . . . . . .

Ambient Temperature Range Storage

–30˚...+65˚C

. . . . . . . . .

Control Module

Mod.

500LC–47CM*

Mod.

500LC–48CM*

Mod.

500LC–49SS*

Control Module

AC

DC

AC

DC

AC

DC

120V AC

1.90

1.60

3.70

24V AC & DC

0.85

0.36

0.34

0.38

0.70

0.72

240 / 277V AC

4.00

2.50

6.00

12V AC & DC

0.60

0.32

0.34

0.36

0.68

0.70

Advertising