Installing Bulletin 500LC Lighting Contactors

14

Publication 500LC–IN001A–EN–P May 2005

Bulletin 500LC Lighting Contactors containing

both N/O & N/C contacts with Field Installed Modifications

GENERAL NOTES

A.

WHEN 500LC COIL AND LINE VOLTAGE ARE THE SAME THE 500LC CONTROL VOLTAGE CAN BE DERIVED FROM THE LINE POLES OF
THE 500LC LIGHTING CONTACTOR.

B.

MAIN CONTACTS ARE SHOWN WITH LOWER CONTACTS IN OPEN POSITION WITH CONTROL LINE DE–ENERGIZED.
(500LC SHIPPED WITH LOWER CONTACTS IN CLOSED POSITION.)

C.

LINE AND LOAD TERMINALS ARE REVERSIBILE.

D.

CONTACTS ARE SINGLE THROW, DOUBLE BREAK, WITH MOMENTARILY ENERGIZED SINGLE COIL OPERATOR MECHANICALLY
HELD IN BOTH OPEN AND CLOSED POSITIONS.

E.

INDICATES CUSTOMER CONNECTION POINTS. ● INDICATES FACTORY CONNECTION POINTS.

F.

CONNECTION POINTS THAT HAVE BOTH CUSTOMER AND FACTORY CONNECTIONS ARE SHOWN AS CUSTOMER CONNECTIONS.

G.

CUSTOMER CONNECTIONS TO LINE AND LOAD WILL ACCEPT NO 10 AWG TO 18 AWG COPPER WIRE.

H.

CUSTOMER CONNECTIONS TO ELECTRONIC MODULE MOD. 500LC–47CM*, 500LC–48CM*, 500LC–49SS* WILL ACCEPT NO. 12
AWG TO 22 AWG COPPER WIRE.

I.

LEADS ON CONNECTORS FOR MOD. 500LC–141C & 500LC–142C ARE NO. 18 AWG. (12” LONG).

J.

CR CONTROL SUPPLIED BY CUSTOMER.

AUXILIARY

CONTACT RATING

10A, 1/3 HP

277 VAC

0.5A, 125 VDC

0.25A, 250 VDC
500LC–141C (1PDT)

500LC–142C (2PDT)

2 WIRE CONTROL MOD. 500LC–47CM*

3 WIRE CONTROL MOD. 500LC–48CM*

START–STOP (FORM 3) CONTROL MOD. 500LC–49SS*

MOD.

500LC–47CM*,

500LC–48CM*, or

500LC–49SS*

LC

BULLETIN 500LC LIGHTING CONTACTOR

(WHEN USED WITH UL67 LISTED PANELBOARD)

IS SUITABLE FOR USE IN A CIRCUIT CAPABLE

OF DELIVERING NOT MORE THAN THE RMS

SYMMETRICAL CURRENT AT THE MAXIMUM

VOLTAGE SHOWN BELOW, WHEN PROTECTED

BY A 30 AMP CIRCUIT BREAKER HAVING AN

INTERRUPTING RATING NOT LESS THEN

VALUES SHOWN.