Installing Bulletin 500LC Lighting Contactors

4

Publication 500LC–IN001A–EN–P May 2005

Line and load terminals are reversible. The Bulletin 500LC

Lighting Contactor is UL Listed for use with 60 or 75˚ C wire. All

power wires should enter enclosure adjacent to the 500LC

terminals. Combination knockouts are provided on Type 1

enclosures. Line and load connections are supplied with clamp

type terminals. These terminals accept the wire sizes #18–10

AWG Cu. Insert appropriate line and load wires and tighten clamp

screws to 18 inch–pounds.

Control Line Connections

Control circuit connections designated L, O, C on the right side are

supplied with clamp type terminals. These terminals accept wire

sizes #18–10 AWG Cu. Simply insert appropriate control wires

and tighten terminal clamp screws to 18 inch–pounds. See the

wiring diagrams.

Install overcurrent protective devices

for the control circuit in accordance

with applicable electrical codes.

Table D lists the maximum distances and minimum wire sizes that

can be run between a control station and one Bulletin 500LC.

Table D – Control Line Run

Wire Size

Maximum Distance (feet) at AC control voltage

(AWG)

120V

240V

277V

347V

480V

14

1,050

3,100

4,100

5,600

8,800

12

1,670

5,000

6,600

9,000

14,000

10

2,650

8,000

10,600

14,000

22,000

Do not exceed these distances for

proper unit operation.

Table E lists the Bulletin 500LC Lighting Contactor’s coil inrush

current and minimum control circuit fuse sizes.

Table E – Inrush Current / Minimum Fuse

Inrush Current Over Fuse Size (amps RMS) at AC control voltage

Amps

120V

240V

277V

347V

480V

inrush

5.0

2.5

2.2

1.8

1.3

fuse

2.0

1.0

1.0

0.75

0.5