Installation instructions, Technical specification, Safety ratings – Rockwell Automation 440N SensaGuard Magnetically Coded NonContact Switch (MC2) User Manual

Page 3: Physical characteristics, Outputs, Response time, Environmental, Protection

Advertising
background image

1. Installation Instructions

Installation must be in accordance with the following steps and stated specifications and should be carried out by suit-
able competent personnel. The unit is not to be used as a mechanical stop. Guard stops and guides must be fitted.
Adherence to the recommended maintenance instructions forms part of the warranty.

This device is intended to be part of the safety related control system of a machine. Before installation, a risk assess-
ment should be performed to determine whether the specifications of this device are suitable for all foreseeable opera-
tional and environmental characteristics of the machine to which it is to be fitted. Refer to Technical Specifications for
Certification information and ratings.

ATTENTION:

The presence of spare actuators compromise the integrity of the safety systems. Personal
injury or death, property damage or economic loss can result. Appropriate management con-
trols, working procedures and alternative protective measures should be introduced to control
their use and availability.

WARNING:

Do not defeat, tamper, remove or bypass this unit. Severe injury to personnel could result.

2. Technical Specification

2.1

Safety Ratings

Standards

EN1088,ISO14119, IEC/EN60947-5-3

Safety Classification

Dual contacts suitable for Cat.3 or 4 systems

Functional Safety Data

B10d: > 2 x 10

6

operations at min.

Usable for ISO 13849-1:2006 and IEC 62061. Data other

PFH

D

: > 3 x 10

7

than B10d is based on: Usage rate of 10p/10mins.,

MTTFd: > 385 years

24 hrs/day, 360 days/year, representing 51840 operations

Dual channel interlock may be suitable for performance

per year.

levels PLe or PLd (according to ISO 13849-1:2006) and for
use in SIL2 or SIL3 systems (according to IEC 62061)

Note: For up-to-date information, visit www.ab.com

depending on application characteristics.

Certifications

CE marked for all applicable directives, cULus, and TUV

2.2

Operating Characteristics (at rated temperature range)

Make, minimum

Break, maximum

Sensing distance horizontal plane of operation

10mm

25mm

Sensing distance vertical plane of operation

6mm

20mm

Typical misalignment

±4mm (see Misalignment Graphs)

Operational Current

30mA + 1 Aux

Maximum # of switches, connected in series

Monitoring Relay Unit dependent (see Section 10)

Operating Voltage

24V dc +10% / -15% (see Section 9)

2.3

Physical Characteristics

Case Material

ULTRADUR

Actuator Material

ULTRADUR

Colour

Red

2.4

Outputs

Safety Output (Solid State Relay)

2 x N.C. 50mA

Auxiliary

1 x PNP N.O. 200mA

2.5

Response Time

Switch response time

5ms

Series response time

5ms

Maximum Frequency of Operation

1Hz

2.6

Environmental

Operating Temperature

-10…+55°C (+14…+131°F)

Operating Humidity

5% -95% relative

Washdown rating / Enclosure type rating

NEMA 3, 4X, 12,13, IP67, 68 & 69K

Shock & Vibration

IEC680068-2-27 30 g, 11ms
IEC680068-2-6 10…55Hz

E.M.C.

EN 61000-6-2, EN 60947-5-3

2.7

Protection

Safety Output Short-Circuit Protection

Provided by the approved safety Relays (See section 10)

Auxiliary Overload Protection

Internal Resettable Fuse

24V Supply Reverse Polarity Protection

Incorporated

Electrical Life

1 x 10

6

cycles

72697 Issue 4 EO: 28485

Magnetically Coded Non Contact Switch Installation Instructions 3