8. Power Supply Requirements

24V dc +10%/-15% has to be supplied by a power supply that complies with IEC / EN 60204 and IEC / EN 61558-1.
Such a power supply meets the electrical safety requirements and maintains the minimum power of
20.4V dc during 20ms even in the event of voltage dips.

When using an approved Relay with an MC2 and the same power supply is utilised for all devices the
Relay will provide surge protection for the MC2. If a separate power supply is used for the MC2 then
extra protection will be required.

9. Approved Monitoring Relay Units

1.

MC2 can only be used with the approved Relays, use of other devices not
listed is at the users own risk.

2.

Only 24Vdc MSR Relays or MSR Relays configured for 24Vdc operation are
compatible with MC2.

9.1

Approved Monitoring Relay Unit List and maximum number

of series MC2s

Monitoring Relay Series

Catalogue Part No.

Maximum number of

MC2 units in series

24Vdc Supply Voltage

MSR Series

-5%

-10%

-15%

MSR30RT/RTP

440R-N23197/440R-N23198

10

10

10

MSR 100 Series

MSR121RT

440R-J23102

8

-

-

MSR123RT

440R-J23106

8

-

-

MSR124RT

440R-G23110/440R-G23108/440R-G23107

10

10

10

MSR126T/R

440R-N23117/440R-N23123

10

10

10

MSR126.1T/.1R

440R-N23114/440R-N23120

10

10

10

MSR127T/TP

440R-N23126/440R-N23132

10

10

10

MSR127R/RP

440R-N23129/440R-N23135

10

10

10

MSR131RTP

440R-C23139

10

10

10

MSR138DP

440R-M23151

10

10

10

MSR138.1DP

440R-M23084

10

10

10

MSR142RTP

440R-G23216

10

8

-

MSR144RTP

440R-C23205

10

10

10

MSR178DP

440R-M23227

10

10

10

MSR 200 Series

MSR210P

440R-H23176

10

10

10

MSR220P

440R-H23177

10

10

10

MSR300 Series

MSR320P connected to a

440R-W23218

10

10

10

MSR310 or MSR312

Note: For up-to-date information, visit www.ab.com

9.2

Safety Ratings

1. An MC2 can achieve up to Cat 4/PLe, SIL CL3 when individually monitored by an approved

Monitoring Relay Unit (see 9.1) that itself achieves Cat 4/PLe, SIL CL3.

2.. Two or more MC2 Sensors connected in series with an approved Relay achieves up to

CAT3/PLd/SIL CL2.

72697 Issue 4 EO: 28485

8

Magnetically Coded Non Contact Switch Installation Instructions

Note: Refer to Technical Specifications for Certification information and ratings.