Installations and Dimensions

see page 9, Fig. 6 / 7 / 8

Wiring the Main Circuit

see page 8

825-M* and 825-MCM*

without main current

transformer

Fig. 1

825-M* and 825-MCM* with

main current transformer

Fig. 2

825-M* and 825-MCM* with two-

phase main current transformer

and summation current trans-

former

Fig. 3

Summation current transformer:

Output current 5-500 mA, Connection k / l

Input module type:

825-MCM2

825-MCM20

825-MCM180

825-MCM630

825-MCM630N

Option 825-MMV

Fig. 5 a)

1T1 / 1T3 / 1T2...6T1 / 6T3 / 6T2

Inputs PT100 # 1...PT100 # 6

Temperature monitoring stator

winding and motor bearings.

Leads up to 10 m twisted, over

10 m screened.

Connect screen to xT2.

7T1 / 7T3 / 7T2

Input PT100 # 7

Temperature monitoring of coolant.

Leads up to 10 m twisted, over

10 m screened.

Connect screen to xT2.

Option 825-MLV

Fig. 5 b)

53 / 54

Auxiliary relay Aux # 4:

IEC 400 VAC / 125 VDC

UL / CSA 240 VAC / 125 VDC
I

th

= 4 A

63 / 64

Auxiliary relay Aux # 5:

IEC 400 VAC / 125 VDC

UL / CSA 240 VAC / 125 VDC
I

th

= 4 A

L1 / L2 / L3

Connection of phase voltage of

main circuit for phase sequence

and phase failure protection.

Series fuse 100 mA fast.

Above 400 VAC

(UL / CSA 240 VAC)

with voltage trans-

former.

Option 825-MST

Fig. 5 c)

23 / 24

Auxiliary relay Aux # 1:

IEC 400 VAC / 125 VDC

UL / CSA 240 VAC / 125 VDC
I

th

= 4 A

33 / 34

Auxiliary relay Aux # 2:

50 VAC / 30 VDC
I

th

= 4 A

43 / 44

Auxiliary relay Aux # 3:

50 VAC / 30 VDC
I

th

= 4 A

I+ / I-

Analog output of thermal motor

load, motor temperature (PT100),

motor current

4...20 mA, 0...300 W

- Indicating meter 825-MTUM

- PLC input

- Recorder

Leads up to 100 m twisted, over

100 m screened.

Y31 / Y32

Control Input # 1:

24 VDC / 24 VAC

Y41 / Y42

Control Input # 2:

24 VDC / 24 VAC

T1 / T2

PTC connection, max. 6 PTC in

series.

Leads up to 100 m twisted, over

100 m screened.

Connect screen to T2.

m

200 300 400 600 1000

mm 20.5 0.75 1 1.5 2.5

k / l

Input to summation current

transformer 5...500 mA.

Basic unit 825-M*

Fig. 5 d)

A1- / A2+

AC supply:

Voltage as printed on AC module,

see 1 Fig. 4.

DC supply:

Voltage as printed on DC module,

see 1 Fig. 4.

Note potential.

Y11 / Y12:

Emergency start of thermal trip

with push button or key-switch.

Y11 / Y13

Means of blocking settings with

jumper, push button or key-switch.

Y21 / Y22

Remote reset with push button or

key-switch.

13 / 14

Alarm contact:

IEC 400 VAC / 125 VDC

UL / CSA 240 VAC / 125 VDC
I

th

= 4 A

95 / 96 / 97 / 98

Main relays:

95 / 96 NC contact

97 / 98 NO contact

IEC 400 VAC / 125 VDC

UL / CSA 240 VAC / 125 VDC
I

th

= 4 A

When the main relay

MR is connected in the

non-fail-save mode, then

the terminal markings on

the unit have to be

adapted using the

marking strip

supplied.

Main current

transformer:

n A / 1 A

n A / 5 A

Input module

type:

825-MCM2

825-MCM20

Main current

transformer:

n A / 1 A

n A / 5 A

Input module

type:

825-MCM2

825-MCM20

Wiring the Control Circuit

see page 8

All installations, commissioning and maintenance must be carried

out by qualified personnel, taking local regulations into account.

Pay attention to the System Manual.