Node Commissioning using Hardware

The ArmorStart is shipped with the hardware rotary switches set to a value
of (99). If the switches are set to a value of (64) or above, the device will
automatically configure itself to the software node address. If the switches
are set to a value of (63) or less, the device will be at the node address
designated by the switch configuration.

To set an address using the hardware rotary switches, simply set the
switches to the desired node address. To access the node address rotary
switches, three-phase and control power should be turned off. Then remove
the starter module from the base unit. The rotary node address switches are
located on the back side of the starter module. Change the switches to the
desired node address. Re-install the starter module to the base unit. Reapply
power and the device will re-start at the new address.

Figure 8 Rotary Node Address Configuration

System Configuration
Information

The following information is provided to identify the default method for
setting up communication to the ArmorStart. Additional configuration
information and advanced settings help can be found in the ArmorStart User
Manual, Publication 284G-UM001*.